HomeMy WebLinkAboutCOM-ELC-26-0061 Plan Corrections Rev1 Department of Development Services Paula Daneluk, Director
Curtis Johnson, Assistant Director
7 County Center Drive T: 530.552.3700
Oroville, California 95965 F: 530.538.7785
buttecounty.ca.gov/dds
This cover sheet provides a summary of the concurrent review of the permit application by all
applicable County departments and divisions. Each department has independently reviewed the
submitted documents for code compliance and project feasibility. The review status for each
department is indicated in the checklist below, and any corrections or conditions identified by
reviewers are attached for reference.
Date: 11/6/2026
Applicant Information: Epic Wireless Group
josh.jordan@epicwireless.net
Assessor Parcel Number: 029-060-020 Address: 4409 Aguas Frias Rd., Richvale, CA 95965
Building Permit Number: COM-ELC-26-0061 Plan Check Cycle: Review #1
Description: INSTALL (N) 30kw Diesel Generator w/ 200G Fuel Tank
*See attached correction letters for the contact information for each department.
Department / Division Status
Building Division Pending Corrections with comments
Planning Division Approved
Fire Department Pending Corrections with comments
Public Works - Land Development Approved
Public Works – Permits Approved
Environmental Health Approved with Comments
SPECIALIST WAITING FOR THE CUSTOMER TO SEND
QUESTIONNAIRE TO AQMD. ONCE THIS HAS BEEN
COMPLETED, SPECIALIST WILL CLOSE THIS REVIEW.
Department of Development Services Paula Daneluk, Director
Curtis Johnson, Assistant Director
7 County Center Drive T: 530.552.3699
Oroville, California 95965
buttecounty.net/dds
November 5, 202
Epic Wireless Group
605 Coolidge Drive
Folsom, CA
Assessor Parcel Number: 029-060-020
Building Permit Number: COM-ELC-26-0061 Plan Check #1
Description: INSTALL (N) 30kw Diesel Generator w/ 200G Fuel Tank
Flood Zone: A per 06007C0950E F.I.R.M. dated January 6, 2011
Sacramento River Designated Floodway – E
Thank you for submitting your building permit application. We have reviewed your documents and listed the
required corrections below. Please provide a written response addressing each comment. Clear and complete
answers will help us approve your project faster. When you are ready, please submit a complete digital set of
revised plans to DSBuilding@buttecounty.net. You can upload larger files directly to www.bcdds.net/drop.
GENERAL COMMENTS:
1. Please respond in writing to each comment by marking this comment list or creating a response letter.
Indicate which detail, specification, or calculation shows the requested information. At minimum, the
following must be included with each plan review response:
1. Page / sheet number(s), detail / specification number(s), etc., and include all applicable code section(s).
2. Briefly explain in writing, how the design is intended to comply with the applicable code sections.
3. Revisions must be identified with a cloud and delta symbol.
Complete and clear responses will expedite the re-check of this project.
2. The plan check fee covers three review cycles. Reviews beyond the third cycle, deferred submittals, and
changes to approved plans will be billed on a time-and-materials basis.
NON-STRUCTURAL COMMENTS:
3. Please correct the panel schedule totals and coordinate the engine block-heater load with the manufacturer’s
specifications. Update the generator load calculation using the coordinated loads. CEC 702.4(A)(2).
4. Coordinate the equipment grounding conductor size with the No. 8 auxiliary circuit conductors. Provide
proportional sizing or substantiate compliance with the exception to CEC 250.122(B).
STRUCTURAL COMMENTS:
1. The flood elevation certificate lists the lowest height of machinery and equipment as 84.8’ with the lowest adjacent
grade listed as 82.0’. The plans show the generator installed directly on the existing concrete slab. Please
demonstrate how the new generator will be raised 2.8’ above the existing ground / slab surface in compliance with
the FEMA Flood Elevation Certificate.
2. Calculations assume a concrete slab thickness of 8”. Please note this thickness requirement on the plans.
FLOOD ZONE COMMENTS:
1. Please place the following information on the plans:
a. Flood Hazard Zone: A
b. Base Flood Elevation: 82.5’
c. Lowest Elevation of Machinery and Equipment: 84.8’
d. Lowest Adjacent Grade: 82.0’
2. The Central Valley Flood Protection Board locates the new generator at 39.4644778, -121.859105. The FEMA
Flood Elevation Certificate locates the new generator at 39.458931, -121.859105. Please coordinate.
3. Please indicate in a prominent location on the plans that a finished construction flood elevation certificate is
required prior to final approval of the structure. (Butte County Code Chapter 26, Ordinance # 4041)
The Department of Development Services is currently open to the public from 8:00 am to 4:00 pm. If you wish
to discuss these plan check comments, please call during our business hours or contact us by e-mail at the
address below.
Jordan Debrunner Michael Main, P.E.
Plans Examiner Plan Check Engineer
530.552.3647 530.552.3655
jdebrunner@buttecounty.net mmain@buttecounty.net
Butte County Fire Department
Office of the Fire Marshal
176 Nelson Avenue Oroville, CA 95965
Office (530) 538-7888
www.buttecounty.net/fire
COMMERCIAL PLAN
REVIEW LETTER
October 27, 2026
Harris Landowning Corp.
4409 Aguas Frias Rd.
Richvale, CA 95965
APN: 029-060-020
Building Permit Number: COM-ELC-26-0061
Description: INSTALL (N) 30kw Diesel Generator w/200G Fuel Tank
Occupancy Classification: U
Dear Applicant,
The plans you recently submitted have been reviewed by the Fire Department
referencing the 2025 edition of the California Building and Fire Codes (CBC and CFC).
The numbered comments listed below in the body of this letter must be addressed in
writing prior to Fire Department Approval of your project.
1. Sheet A-1.1, Site Plan, Add a note and illustrate on Sheet A-1.1 the use of a
Knox Padlock or Knox Box for fire department access into the compound.
Product information and ordering available on www.knoxbox.com or contact
the Butte County Fire Marshal Office at 530-538-6320 for more information.
The Fire Marshal's Office is open 8:00 a.m.–5:00 p.m. if you have any questions
pertaining to this permit. Please call during business hours or email the address below.
Permit status may be tracked at the Accela Citizen Access portal: Butte County Accela
ACA.
Troy Hand Marnie Gedney
Deputy Fire Marshal Fire Protection Planning
530.538.6320 530.538.6320
troy.hand@fire.ca.gov marnie.gedney@fire.ca.gov